Communications Cable

Penetration Item (Size and Type)

Sleeve
O = Optional
R = Required

Point Contact

Assembly Thickness

F Rating

Nelson Product

UL System

Nelson FS Drawing

25 pr. pvc insulated      5 2 CLK W-J-3010 FS-0101
15% fill, 25 pr. #24 AWG  R   2 PLW C-AJ-3093 FS-0130
15% fill, 25 pr. #24 AWG      3 FSP C-AJ-3003 FS-0002
50 pr. #24 AWG      5 2 FSP W-J-3007 FS-0079
200 pr. #24 AWG copper conductor     6 2 FireBrick W-J-3159 FS-0664
13% fill, 100 pr. #24 telephone      3 FSP C-AJ-3004 FS-0014
400 pr. #24 AWG comm.    X 2 2 LBS3 W-J-3118 FS-0577
400 pr. #24 AWG comm. Cable bundles w/ more      3 2 ES1399 C-AJ-8118 FS-0377
38% fill, 400 pr. #24 AWG  O   2 LBS3 C-AJ-3224 FS-0533
40% fill, 400 pr. #24 AWG  O   3 LBS3 C-AJ-3227 FS-0535
30% fill, 5 pr. #24 AWG  R   5 2 CLK C-AJ-3094 FS-0131
25% fill, 25 pr. #24 AWG  R   5 2 LBS3 W-J-3115 FS-0574
25% fill,100 pr. #24 AWG      5 2 ES1399 C-AJ-3235 FS-0631
33% fill, 100 pr. #24 AWG  O   2 LBS3 C-AJ-3225 FS-0532
40% fill,100 pr. #24 AWG  R   6 2 FSP W-J-3075 FS-0383
70% fill., 100 pr. #24 AWG  O   5 2 PCS/FSP C-AJ-3118 FS-0196
100% fill, 100 pr. #24 AWG      2 MPS C-AJ-3047 FS-0087
100% fill, 100 pr. #24 AWG      2 MCT C-AJ-3048 FS-0114
100% fill, 100 pr. #24 AWG  R   6 2 PLW/FSP W-J-3100 FS-0491
36% fill, 240 pr. #24 AWG      8 2 CPS/FSP C-BJ-4016 FS-0094
45% fill, 400 pr. #24 AWG telecomm.  O-PVC   3 LBS3 C-AJ-3289 FS-0669
45% fill, RG59/U, RG/6 COAX  O-PVC   3 LBS3 C-AJ-3289 FS-0669
45% fill, 62.5/125 Fiber optic  O-PVC   3 LBS3 C-AJ-3289 FS-0669
24 Fiber optic    X 6 2 LBS3 W-J-3116 FS-0575
62.5/125 Fiber optic  R X 6/1/2008 1,2 LBS3 W-J-3119 FS-0578
40% fill, 62.5/125 Fiber optic  O   3 LBS3 C-AJ-3227 FS-0535
72 Fiber optic  R   2 FSP C-AJ-3089 FS-0126